Al/PVC/CuT/STA/PVC 3,6/6 kV, АВЭВБбШв-6
POWER CABLES 3,6/6 kV
Al/PVC/CuT/STA/PVC 3,6/6 kV (Наш аналог кабель АВЭВБбШв-6)
Standard: TU U 31.3-23075526-008:2008
Construction:
1. Conductor: aluminum (1, 2 class);
2. Core Insulation: PVC;
3. Screen: aluminum or copper tape;
4. Filling: PVC;
5. Belt insulation: PVC;
6. Armour: steel tapes;
7. Sheath: PVC;
8. Ground conductor: copper.
Application:
Cables are intended for transmission and distribution of electric power in fixed installations at rated voltage of 6 kV at 50 Hz frequency. Installation and operation - in the ground (in trenches) with low corrosivity, where protection is required against mechanical damage without significant tensile forces.
Technical parameters:
Rated operational voltage: 3,6/6 kV;
Range of cross-sections 25 – 400 mm²;
Number of cores: 1; 3; 3+1(ground conductor);
Shape of conductor: round;
Оperating temperatures - of -50 °С to +50 °С;
Conductor temperature: max. +70 °С;
Relative humidity: 98% at 35 °C temperature;
Flame retardant: IEC 60332-1;
Service life: 30 years.
Nominal mail cross-section (mm²) |
Number of cores |
Number of wires in the core |
10 – 120 |
1; 3; 3+1 |
1 |
50 – 95 |
1; 3; 3+1 |
7 - 19 |
120 - 240 |
1; 3; 3+1 |
19 - 37 |
150 - 240 |
1; 3; 3+1 |
37 |
300-800 |
1 |
37-61 |
Range sections of the ground conductor: 10 – 70 mm². Number of ground conductor: 1, 2 or 3. |
Variants of execution:
АВЭВБбШвнг-6:
АВЭВБбШвнг-LS-6: flame retardant - IEC 60332-3 (category A), IEC 61034-2, IEC 60754-1,IEC 60754-2.
АВЭВКбШв-6 (Al/PVC/CuT/SWA/PVC 3,6/6 kV): steel wire armour.- 10.02.2017Foreign counterparts of the cable and wire produced in our factory
- 17.01.2017The warranty period and service life of cables and wires Cable Factory production "Energoprom"